| Item | Qty | Unit |
|---|---|---|
| AC Circuit Breakers & Distribution Tomzn brand, 415V AC, MCCB | 8 | Each |
| DC Earth, complete as described in Para 24.16 of the Specifications. with 30 SWG. copper conductor, supply and fixing. | 9 | Each |
| AC Earth, complete as described in Para 24.16 of the Specifications. with 30 SWG. copper conductor, supply and fixing. | 10 | Each |
| Installation Accessories Connectors, conduits, cable ties, junction boxes | 11 | Each |
| Civil & Foundation Works RCC pedestals, roof preparation, waterproofing | 12 | Each |
| Mechanical Installation Structure erection, module mounting | 13 | Each |
| Electrical Installation & Commissioning | 14 | Each |
| Transportation & Logistics | 15 | Each |
| Add 11% above on mes Shedule of rates 2025 | 16 | Each |
| Supply, installation, testing and commissioning of PV Panel Tier-I for Hybrid Solar Electric Energy System. |
| 1 |
| Watt |
| Supply, installation, testing and commissioning of Lithium Iron Phosphate Battery for Solar Electric Energy System. | 2 | Watt |
| Supply and Installation of GI/Aluminium Frame Structure (Roof Top Elevated Structure) including concrete work. | 3 | Watt |
| Micro Project - Engineering, Procurement, Construction, Installation, Testing, Commissioning and successful completion of On- grid/Hybrid Solar PV Systems at 8 x Cantonment Boards (Kharian, Shorkot, Attock, Kamra, Pano Aqil, Mangla, Zhob, Loralai) | 1 | — |
| 3 phase Hybrid Sineng Inverter with Remotely Monitoring Devices | 1 | kW |
| Tier 1 Manufacturer according to bloomberg latest issued rankings with IEC 61215 Compliance and not less than 600 W N-Type Half Cut PV module | 2 | kW |
| Roof Top Galvanized Elevated Structure | 3 | kW |
| Lithium-ion Battery for critical load installed with Hybrid system | 4 | kW. |
| Supply & fixing of Geset Gateway / Synch Controller, completed with all aspects | 5 | Job |
| IP65 galvanized iron AC combiner Cabinet, 1 IN 1 Out The size of cabinet : H*L*D ft (4*2.5*2.5)/ DB as per layout Gauge : 16 AWG, Color : RAL 6021 Mounting type = ground mounted Details of breakers and SPD to be in housed in cabinet, Others specs:RYB Indicator, Digital Ammeter and Voltmeter =Yes, AC grounding bus bar =Yes(length =1 ft, to be placed at the left bottom of the DB),DC grounding Bus bar=Yes | 6 | Nos. |
| IP54 GI DB for each inverter for placing DC strings Wall mount, single door with lock and with complete fitting scheme/ railing for DC breakers | 7 | Nos. |
| AC Breakers 160A | 8 | Nos. |
| AC Breakers 250A | 9 | Nos. |
| 06 mm Sq. DC flexible wire 1500V DC Copper conductor, Cu XLPO/XLPEO | 10 | Mtr. |
| AC Cable 4-C Cu, PVC/PVC 0.6/1 kV, 95 mm Sq. AC stranded | 11 | Mtr. |
| AC Cable 4-C Cu, PVC/PVC 0.6/1 kV, 16 mm Sq. AC stranded | 12 | Mtr |
| Complete earthing of Solar System including lighting arresters with 15mm dia copper, 150 cm long with copper base, 75mm x 40 mm x 30 mm, fixed complete with brass, bolts, supply and fixing | 13 | Nos. |
| 16 AWG Galvanized iron with flat cover, perforated, size (W*D)inch 4*2 for laying string wires | 14 | Mtr |
| DB’s for Energy Source and Load for Back equipment, Racks for BESS, completed with all aspects | 15 | Nos. |
| Net Billing Services complete in all aspects along with bidirectional meters and NEPRA license | 16 | Job. |
| S/F of UPVC pipe including band, sockets and clips as per site req. | 17 | Job |
| Change Over (300A) | 18 | Job |
| 5% above on MES Schedule 2025 | 19 | Job |
| S/F of Solar Panels using 1 brand N-Type Mono PERC (620Watt/Each) | 1 | Watt |
| Hybrid inverter | 2 | Watt |
| Supply and Installation of GI/ Aluminium frame structure (Roof Top Elevated Structure) 3 including concrete work for solar electric energy system, complete in all respect as specified | 3 | Watt |
| 4 DC Cabling & Connectors with all as spd. | 4 | Mtr |
| Cable electric HT. 11 KV stranded copper conductor, XLPE insulated, extruded, PVC bedded, steel wire armoured and 5 PVC sheathed overall, Single core, 16 mm2 Laid in GI/RCC pipe duct (excluding cost of pipe duct), supply and fixing. | 5 | Mtr |
| Earthing & Lightning Protection withh all as spd. | 6 | Job |
| Add 10% above on MES Sch of Rate 2025 | 7 | Job |
| Supply, installation, testing and commissioning of PV panel Tier-I for HYBRID solar electric energy system, 15KW : LONGI/JA/Jinko/Canadian complete in all respect as specified. | 1 | Watt |
| Supply, installation, testing and commissioning of Hybrid Solar Inverter (Solar + National Grid dual-input, 3-phase output), rated 15 KW, tier-1 (USA/Europe/China or equivalent), MPPT charge controller, IP65, automatic grid- fallback on low solar output, complete in all | 2 | Watt |
| Supply and Installation of GI/Aluminium frame structure (Roof Top Elevated Structure) including concrete work for solar electric energy system, complete in all respect as specified. | 3 | Watt |
| Supply, installation, testing and commissioning of DC Cable 6mm² double XLPO insulated and tin coated for solar electric energy system, complete in all respect as specified. | 4 | Mtr |
| Change over switch, 60 A, TP with NL, wall mounted type, supply and fixing. (Sized for ~15kW/24A full-load current with margin — confirm against actual inverter output rating.) | 5 | Each |
| MCCB 4 Pole, 500/600 V, 50/60 Cycles, complete with thermal and magnetic trip, 60 to 100 A breaking capacity, supply and fixing. | 6 | Each |
| Air termination for Lightning Conductor, with 15 mm dia copper rod, 150 cm long, with gunmetal copper base, 75 mm x 40 mm x 30 mm, fixed complete, with brass bolts, supply and fixing. | 7 | Each |
| Inspection joints, cross, tee, straight as per site requirement, supply and fixing. | 8 | Each |
| PVC conduit, 25 mm dia, complete with all bends, tees, boxes, saddles etc for Surface wiring, and concealed wiring, supply and fixing. | 9 | Metre |
| PVC conduit, 50 mm dia, complete with all bends, tees, boxes, saddles etc for Surface wiring, and concealed wiring, supply and fixing. | 10 | Metre |
| Down conductor, roof conductor and conductor required for bonding exposed metal work to earthing conductor with copper strips, 25 mm x 3 mm, supply and fixing. | 11 | Metre |
| Earth for Lightning conductor, complete as described in Para 24.19.6(2) of the Specifications, inclusive of copper strip upto test joint, supply and fixing. | 12 | Each |
| Earth, complete as described in Para 24.16 of the Specifications, with 6 SWG copper conductor, supply and fixing. | 13 | Each |
| Cable electric LT, PVC insulated, PVC sheathed, un-armoured, overall PVC 600/1000 V, with stranded Copper conductor, 16 mm², 4 core, laid in GI/RCC pipe/duct (excluding cost of pipe/duct), supply and fixing. (Sized for ~15kW/24A load — smaller cross-section than the 35mm² used for 50kW systems.) | 14 | Metre |
| Complete documentation & commissioning process (as applicable — no DISCOM net- metering / bi-directional meter required, as this hybrid system does NOT export to the grid). Proper Earthing. Panel to Panel earthing with proper thimbles, nuts & bolts and Cable. | 15 | Job |
| Add 10% above on MES SCH 2025 | 16 | Job |
| Supply, installation, testing and commissioning of PV panel Tier-1 for Hybrid solar electric energy system, complete in all respect as specified. 36x1000w | 1 | Watt |
| Hybrid Solar Inverter 12KW LIVOLTEK HPI-12KS2, 121W, IP66 | 2 | Each |
| Supply, Installation, testing and commissioning of Lithium Iron Phosphate Battery for solar electric energy system, complete in all respect as specified. | 3 | Watt |
| Supply and Installation of GV Aluminum frame structure (Roof Top Elevated Structure) including concrete work for solar electric energy system, complete in all respect as specified | 4 | Watt |
| DC Solar Cable (4 mm²) 1,500V DC rated, UV-resistant, 90m coil | 5 | Coil |
| Supply, Installation, testing and commissioning of DC Cable 6mm² double XLPE insulated and tin coated for solar electric energy system, complete in all respect as specified. | 6 | Mtr |
| DC Breakers | 7 | Each |
| AC Breaker | 1 | Nos. |
| DC Wire with PV | 50 | Mtr. |
| AC Wire | 0 | Mtr. |
| S/F of Solar Panels using 1 brand N-Type Mono PERC (620Watt/Each) | 50000 | Watt |
| Hybrid inverter | 50000 | Watt |
| Supply and Installation of GI/ Aluminium frame structure (Roof Top Elevated Structure) 3 including concrete work for solar electric energy system, complete in all respect as specified | 50000 | Watt |
| 4 DC Cabling & Connectors with all as spd. | 500 | Mtr |
| Supply, installation, testing and commissioning of DC Cable 6 mm Double XLPO insulated and tinned copper conductor. | 4 | Mtr |
| Change Over Switch, 400 A, TP with NL, wall mounted type, supply and fixing. | 5 | Each |
| MCCB 4 Pole, 400 A, 500/600 V, supply and fixing. | 6 | Each |
| PVC Conduit, 25 mm dia, complete with accessories, supply and fixing. | 7 | Metre |
| PVC Conduit, 50 mm dia, complete with accessories, supply and fixing. | 8 | Metre |
| Cable Electric LT, PVC insulated, PVC sheathed, un-armoured, 35 mm, 4 Core, laid in GI/RCC pipe/duct, supply and fixing. | 9 | Metre |
| Supply, Installation, Testing & Commissioning of 12 kW Three Phase Hybrid Solar Inverter, complete with monitoring, protection devices and commissioning. | 10 | Job |
| Supply, Installation, Testing & Commissioning of Complete Earthing & Lightning Protection System for 12kW Hybrid Solar System. | 11 | Job |
| Add 10% above on MES Sch. of Rates 2025 | 12 | Job |
| Supply, installation, testing and commissioning of PV panel Tier-I for solar electric energy system, complete in all respect as specified. | 1 | Watt |
| Supply, installation, testing and commissioning of PV panel Tier-I for Hybrid solar electric energy system, complete in all respect as specified. | 2 | Watt |
| Supply and Installation of G/V Aluminium frame structure (Roof Top Elevated Structure) including concrete work for solar | 4 | Watt |
| Supply, installation, testing and commissioning of DC Cable 6mm² double XLPO insulated and tin coated for solar Arrary 1(Mppt) strings Arrary 2(Mppt) strings | 5 | mtrs |
| Cable tray out of 16 Guage, Gl sheet, without cover, complete in jointing plates. Cable tray size 12" x 3". | 6 | mtrs |
| Cable electric LT, 600/1000 V, stranded aluminium conductor, insulated extruded, PVC bedded, steel wire armoured and PVC | 7 | — |
| MCCB 6-63 A | 8 | No |
| MCCB 6-63 A Doyble Pole | 9 | No |
| Bus bar chamber, 600/610 mm long, steel sheet / Cl with hinged cover, hard drawn copper bus bars mounted on well insulated with micanite or other approved insulating material frames, complete with main and branch cables, socket and terminals, enamel paint inside and black outside, 500 V, 60/100 A, 4 bars, 400 mm height, 175-225 mm depth, supply and fixing. | 10 | Each |
| MCCB 4 Pole, 500 / 600 V, 50/60 Cycles, complete with thermal and magnetic trip 1000A (Breaking capacity 70 KV), supply and fixing. | 11 | Each |
| Earth, complete as described in Para 24.16 of the Specifications, with 30 SWG copper conductor, supply and fixing. | 12 | Each |
| Earth for Lightning conductor, complete as described in Para 24.19.6(2) of the Specifications, inclusive of copper strip upto test joint, supply and fixing. | 13 | Each |
| Steel Box (16 BG) for main switch, distribution board and meter, Type A as per drawing in Figure 25-14, duly painted with primer and two coats of synthetic enamel paint, supply and fixing. | 14 | Each |
| Supply and Installation of GI/ Aluminium frame structure (Roof Top Elevated Structure) including concrete work for solar electric energy system, complete in all respect as specified. | 4 | Watt |
| Supply, installation, testing and commissioning of DC Cable 6mm² double XLPE insulated and tin coated for solar Array 1(Mppt) strings | 5 | mtrs |
| Cable tray out of 16 Guage, GI sheet, without cover, complete in jointing plates. Cable tray size 12' x 3'. | 6 | mtrs |
| Cable electric LT, 600/1000 V, stranded aluminium conductor, insulated extruded, PVC sheathed overall single core, 70 mm2 laid in trenches complete with bricks, sand (excluding cost of excavation) supply and fixing. | 7 | mtrs |
| MCCB, SP, 6 to 63 A. (Breaking capacity 6 KA), supply and fixing Inverter main (D.B) | 8 | Each |
| MCCB, SP, 6 to 63 A. (Breaking capacity 6 KA), double pole supply and fixing Inverter main (D.B) | 9 | Each |
| Bus bar chamber, 600/610 mm long, steel sheet / CI with hinged cover, hard drawn copper bus bars mounted on well insulated with micanite or other approved insulating material frames, complete with main and branch cables, socket and terminals, enamel paint inside and black outside, 500 V, 60/100 A, 4 bars, 400 mm height, 175-225 mm depth, supply and fixing. | 10 | Each |
| Earth, complete as described in Para 24.16 of the Specifications, with 3/0 SWG copper conductor, supply and fixing. | 12 | Each |
| Steel Box (16 BG) for main switch, distribution board and meter, Type A, as per drawing in Figure 25-14, duly painted with primer and two coats of synthetic enamel paint, supply and fixing. | 14 | Each |